Overview
GW1-15, 36/630, 1250: Outdoor integrated high-voltage disconnector with 3-phase linkage, fits side/front mounting. 304 stainless steel/hot-dip galvanized fasteners for high corrosion resistance. T2 copper lines/blades (silver/tin-plated exposed parts) resist electrochemical corrosion, work with copper/aluminum wires. Meets peak/short-time withstand current; suits ≤3000m altitude, -40℃~+70℃. Manual/automatic operation (customizable). Compact, lightweight, easy to install/maintain. ≥3000 mechanical cycles; complies with GB/T 1985-2023, IEC 62271-102.
Normal Service Condition
- Ambient temperature: -40℃ +40℃;
- Altitude: Ordinary type ≤ 1000m, Plateau type ≤ 5000m;
- Wind pressure: not more than 700Pa (equivalent to wind speed 34m/s);
- Anti-pollution level: Level 3;
- Earthquake intensity: not more than 8 degrees;
- Ice thickness: <20mm;
- No fire, explosion, chemical corrosion and frequent severe vibration;
- Exceeding the above conditions requires consultation with the manufacturer.